Solar Panels Series vs Parallel: What Changes?
Solar panels series vs parallel comes down to one trade. Wire panels in series and their voltages add up, while the current stays the same. Wire them in parallel and the currents add up, while the voltage stays the same.
- Plus (+) wire and series link
- Minus (−) wire, dashed
- Arrowheads, on plus and minus wires alike: the way the current runs
Here is what surprises people. Take four 100 W panels and wire them either way. On paper, they make exactly the same power.
But the parallel version sends four times the current down the cable. Heat in a cable grows with the current squared, so that is 16 times the heat in the same cable.
So the choice between solar panels in series or parallel is about three things: your cable, your charge controller and your coldest morning.
What Wiring Solar Panels In Series Does To Voltage
Think of water in a hose. Voltage is like the pressure, and current is like the amount of water that flows.
A series connection is a chain, one panel after the next. Each panel adds its voltage to the total, the way every lego brick makes a tower taller.
For two identical cells in series, Penn State's solar course says the "voltage is doubled, while current remains the same".
Now a real panel. The Renogy RNG-100D-SS is a 100 W panel, and its datasheet (sheet V2.1) lists an open circuit voltage, Voc, of 22.3 V. Its short circuit current, Isc, is 5.86 A.
Wire two of them in series and the Voc becomes 22.3 V + 22.3 V = 44.6 V, while the Isc stays at 5.86 A.
That sum is ours, on one datasheet. Renogy's sheet says the company may change its data without notice, so use the sheet for your own panel.
Our guide to reading a solar panel label explains Voc, Isc and the working pair, Vmp and Imp. On this sheet all four are given at standard test conditions: 1000 W/m2 of light and a cell temperature of 25 C.
Series has a weak spot. TU Delft's solar course says the current in a series string is set by the cell that delivers the smallest current. That is why shading on one panel can affect the output of the whole string.
What Wiring Solar Panels In Parallel Does To Current
A parallel connection puts panels side by side, like several hoses filling one pool. The pressure is the same, but more water arrives.
For two identical cells in parallel, Penn State says the voltage stays the same as for a single cell, while the current adds up.
Take the same two Renogy panels. In parallel the Voc stays at 22.3 V, and the Isc becomes 2 x 5.86 A = 11.72 A.
Series Parallel Solar Panel Wiring: Strings Side By Side
You don't have to pick one. Ohio State University Extension describes how arrays are built. Panels are wired in series strings to increase the voltage, and the strings are then wired in parallel to increase amperage.
With four panels, that setup means two strings of two together, written 2S2P. Here are all three layouts for four Renogy RNG-100D-SS panels, using the sheet's Vmp of 18.6 V and Imp of 5.38 A.
| Wiring of four panels | Working voltage (Vmp) | Working current (Imp) |
|---|---|---|
| All in series | 4 x 18.6 V = 74.4 V | 5.38 A |
| Two strings of two (2S2P) | 2 x 18.6 V = 37.2 V | 2 x 5.38 A = 10.76 A |
| All in parallel | 18.6 V | 4 x 5.38 A = 21.52 A |
These are our sums on the datasheet's test numbers, not measurements on a roof.
Why Higher Voltage Is Easier On The Cable
Look at the first and last rows of that table. Multiply volts by amps and both give 400.272 W.
The power is the same, but the current is not. Victron's wiring book says that for the same power, "The higher the voltage, the lower the current will be".
The same book gives the heat rule: P = I²R. All in parallel carries four times the current of all in series, and 4 x 4 = 16 times the heat in the same cable.
So a parallel array with long cable runs needs thicker cable. EPEver's controller manual says larger wires can be used over a long distance to reduce the voltage drop and improve performance.
Our DC cable size calculator works out the size for your run.
The Cold Morning Check: String Voltage And The Charge Controller
This is the part where a mistake can damage equipment, so take it slowly.
A charge controller sits between the array and the battery, and it has a hard limit for the voltage coming in. Victron's manual for the SmartSolar MPPT 100/30 says the array's maximum open circuit voltage "can not exceed 100V".
Cold is the catch. The same manual says that at ambient temperatures below 25 C the Voc will be higher. So it tells you to count the Voc and its temperature coefficient together.
Try it with four Renogy panels in series. On the label that is 4 x 22.3 V = 89.2 V, which looks fine.
Now assume a morning of minus 20 C. That is our assumption for this example, and it is 45 degrees below the 25 C of the label test.
The sheet lists a Voc temperature coefficient of -0.28%/C, so the rise is 0.28 x 45 / 100 = 12.6 %. Then 89.2 V x 1.126 = 100.4392 V, about 100.44 V.
That is above the 100 V limit, so four in series fail the check. Three in series start at 3 x 22.3 V = 66.9 V and stay under 100 V on the same sum.
- String voltage (Voc), from 0 V
- 100 V limit of the controller
Treat this as an example, not a rule for every 100 W panel. It is a straight-line sum with one maker's coefficient on one datasheet.
For your own place, Morningstar says to calculate the Voc for the record cold temperature at the installation site. Our MPPT charge controller calculator runs this check with your panel, your string layout and your lowest temperature.
There is a floor too. Victron's manual says the PV voltage must exceed Vbat + 5V for the controller to start, and Vbat is the battery voltage.
One more number, and this one is ours. On this site, 48 V nominal is the DIY limit, and that is a battery voltage. A string's voltage is a different number: three Renogy panels in series already have a Voc of 66.9 V.
Makers warn about string voltage in their own words. Victron: "High DC voltage is supplied to the MPPT when a connected PV array is exposed to light". Morningstar says its TriStar charge controller must be installed by a qualified technician.
So plan your strings yourself, and have an experienced installer do or check the wiring of a string above that limit.
Can I Mix 100W And 200W Solar Panels?
Yes, but the wiring decides how well it works. In series, the string runs at the current of the lower panel: PVEducation says the total current "is equal to the lowest current". In parallel, both panels are held to one shared voltage.
Take two real panels. The Renogy panel above has 33 cells, a Vmp of 18.6 V and an Imp of 5.38 A. The Rich Solar RS-M200P is a 200 W panel with 60 cells, a Vmp of 36.3 V and an Imp of 5.51 A.
In series, their working voltages add: 18.6 V + 36.3 V = 54.9 V. The string current is held back by the weaker panel, here the Renogy with an Imp of 5.38 A.
The gap is small: 5.51 A - 5.38 A = 0.13 A, or 2.36 % of the higher figure. For its own modules, a Q CELLS manual says to avoid Imp mismatches of more than 5 % in a series string.
We read the Rich Solar sheet and the Q CELLS manual as copies hosted by a retailer.
But this pair is a lucky case. The 200 W panel gets its extra power from about twice the cells in series, so its voltage is about double while its current stays close to that of the 100 W panel.
In parallel the same pair fits badly. Their Voc ratings are 22.3 V and 43.5 V, and PVEducation says the combined Voc "lies between" the individual ones. At one shared voltage, at least one of the two panels works far from its own Vmp of 18.6 V or 36.3 V.
Parallel is for a mix with matching voltages, such as two 12 V panels of 100 W and 200 W. We read no datasheet for a 12 V 200 W panel, so we give no sum for that pair.
Should You Wire Solar Panels In Series Or Parallel?
It depends on three things: your controller's voltage window, your shade and your cable run. Run through this short list:
- Long cable run: panels in series keep the current lower, and the cable loss with it.
- String voltage close to the controller's maximum: make the strings shorter and wire them in parallel.
- Shade: in a series string the weakest panel sets the current, so look at your shade first.
- Mixed panels: match the currents in series, or the voltages in parallel.
- A string above 48 V nominal: an experienced installer does or checks the wiring.
Series or parallel is not a contest. Add up the numbers on your own label, check your coldest morning, and the right wiring shows itself.
Sources
- Penn State, EME 812 course pages: cells, modules and arrays
- TU Delft OpenCourseWare, Solar Energy, sections 15.1 to 15.3
- Ohio State University Extension, On-Farm Solar Electric System Safety (CDFS-4105)
- PVEducation, Mismatch for Cells Connected in Series
- PVEducation, Mismatch for Cells Connected in Parallel
- Renogy, RNG-100D-SS 100 W panel datasheet, sheet V2.1
- Rich Solar, MEGA 200 PRO (RS-M200P) datasheet, copy hosted by a retailer
- Victron Energy, SmartSolar MPPT 100/30 and 100/50 manual, installation
- Victron Energy, SmartSolar MPPT 100/30 and 100/50 manual, technical specifications
- Victron Energy, SmartSolar MPPT 100/30 and 100/50 manual, safety precautions
- Victron Energy, Wiring Unlimited
- EPEver, Tracer AN G3 series manual V2.0
- Morningstar Tech Tip: solar controller system sizing with 60-cell modules
- Morningstar, TriStar MPPT quick start guide
- Q CELLS, Q.PEAK DUO-G5.X manual (2017-10 Rev01), copy hosted by a retailer
Hard Words
| Term | What it means |
|---|---|
| Series | Panels wired one after the next in a chain. The voltages add up and the current stays the same. |
| Parallel | Panels wired side by side. The currents add up and the voltage stays the same. |
| String | A group of panels wired in series. |
| 2S2P | Two strings of two panels, with the two strings wired in parallel. |
| Voc | Open circuit voltage. The datasheet number you check against the charge controller's maximum. It goes up in the cold. |
| Isc | Short circuit current, a number on the panel's datasheet. |
| Vmp and Imp | The working voltage and working current on the panel's datasheet. |
| Temperature coefficient | The datasheet number that says how much a value changes for each degree of temperature. |
Common Questions
Is it better to wire solar panels in series or parallel?
Neither wins everywhere. Series adds the panels' voltages and keeps the current low, which cuts cable loss, but the string's cold-weather open circuit voltage must stay under the charge controller's maximum. Parallel keeps the voltage low and adds the currents, which calls for thicker cable. You can also combine them: series strings wired in parallel.
Do 12V solar panels need to be connected in series or parallel?
It depends on the battery and the charge controller. Victron's example for a 24V battery on a 100V MPPT controller needs at least 72 cells in series: 2x 12V panel in series or 1x 24V panel. That controller only starts when the PV voltage exceeds the battery voltage (Vbat) + 5V.
Are most solar panels wired in series or parallel?
Inside a panel, the cells are usually in series. TU Delft notes that modern modules often contain 60, 72 or even 96 solar cells that are usually all connected in series. How the panels of an array are wired is the builder's choice: in series, in parallel or as series strings in parallel.
Can I mix panels with different wattages in a single string?
You can, at a cost. PVEducation states that in series the total current "is equal to the lowest current", so the whole string runs at the current of the lowest panel. A Q CELLS manual, for its own modules, says to avoid Imp mismatches of more than 5 % in a series string.
Is it better to have 2 100W solar panels or 1 200W?
We found no source that compares two 100 W panels with one 200 W panel head to head, so we name no winner. It depends on the bypass diode layout of the panels and on how they are wired. Our shading guide explains bypass diodes.
How do you connect 4 solar panels in series and parallel?
As two strings of two, written 2S2P: two pairs of panels in series, and the two pairs in parallel. With four Renogy RNG-100D-SS panels (sheet V2.1), our sum gives a Voc of 2 x 22.3 V = 44.6 V and an Isc of 2 x 5.86 A = 11.72 A.