What LiFePO4 charging voltage should you set on a charge controller or inverter-charger? The makers in the chart below do not print one number, so your own battery's manual decides.
This page is for the battery bank of an off-grid house or cabin. Our LiFePO4 battery guide explains the lithium iron phosphate (LFP) battery itself. Every figure was checked on 18 November 2026 against the sources at the bottom.
The LiFePO4 Battery Charging Voltage Chart, Maker By Maker
Rolls recommends an absorption voltage of 58.4 V for a 48 V system of four of its 12 V LFP batteries in series. Discover's manual gives 54.4 V for its AES 42-48-6650, and adds: "Do not charge battery higher than 3.4 V per cell module."
Same battery class, two very different settings. So the chart lists each maker by name, with nothing averaged.
| Class | Battery and document | Absorption (bulk) voltage | Float voltage |
|---|---|---|---|
| 12 V | Victron Lithium Battery Smart 12.8 V, manual rev 21 01/2026 | 14.20 V | 13.50 V |
| 12 V | Battle Born BB10012, 100 Ah 12 V, data sheet | 14.2 V to 14.6 V | 13.4 V to 13.8 V |
| 12 V | RELiON 12 V system, Charging Instructions 08.28.18 | 14.0 V to 14.6 V | 13.3 V to 13.8 V |
| 12 V | Rolls 12 V LFP, operating manual, PDF dated Apr 2021 | 2-stage: 14.6 V recommended, range 14 V to 14.6 V | 3-stage: 13.6 V, with 14.4 V absorption |
| 48 V | Discover AES 42-48-6650, manual 805-0015 REV C | 54.4 V | 53.6 V, optional |
| 48 V | Fortress Power eVault Max 18.5 kWh, 51.2 V, technical datasheet | 54.4 V | 54 V; inverter charging "2 Stage / No Float" |
| 48 V | SimpliPhi PHI 3.8 kWh 60 Amp, 51.2 V, spec sheet REV073019 | 54.4 VDC | 54 VDC for a charge controller; inverter charging "2 STAGE NO FLOAT" |
| 48 V | Pylontech US5000, operation manual | 52.5 V to 53.5 V charge voltage | no float value in the manual |
| 48 V | RELiON 48 V system, same Charging Instructions | 56.0 V to 58.4 V | 53.2 V to 55.2 V |
| 48 V | Rolls 48 V system of four 12 V LFP in series, same manual (it excludes the S48-6650LFP ESS) | 2-stage: 58.4 V recommended, range 56 V to 58.4 V | 3-stage: 54.4 V, with 57.6 V absorption |
Rolls prints its 3-stage profile for legacy lead-acid chargers. We read the RELiON, Rolls, Fortress, SimpliPhi and Pylontech documents in a copy hosted by a reseller or another third party.
- Absorption (bulk) or charge voltage
- Float, hollow and dashed
- Dot: the recommended value
- Tick: a BMS limit
- Dashed line: the cell limit
On this site, 48 V nominal is the DIY limit. So the 48 V class is the top of this chart, and it includes packs their makers name 51.2 V.
This is not a state of charge chart, the kind that turns a voltage reading into a percentage. For your battery's charge level, see our battery shunt page.
Bulk, Absorption And Float: How The Charge Stages Work
Charging runs in stages, a bit like filling a glass of water. You pour fast, slow down near the brim, then only top it up.
On Discover's charge curve, bulk means the charger sends a constant current until the battery reaches 3.4 V per cell module. In absorption it holds that voltage, and it stops when the current drops below 2 A.
Float comes last: in its initial charge steps, Victron's manual says its battery is fully charged when the charger has reached the float stage and the VictronConnect app shows the cells as balanced. If a charger asks for a bulk voltage, Victron says to set it equal to the absorption voltage.
How long should absorption last? Victron's manual gives 2 hours for its Lithium Battery Smart, while Battle Born's sheet gives 30 minutes per 100 Ah battery bank.
For Fortress batteries we have two documents. The eVault Max 18.5 kWh datasheet gives 60 minutes of absorb time, while a Morningstar technote for the Fortress LFP-10 and eVault 16.5 gives 6 min.
Victron gives a reason for its 2 hours: the manual says cell balancing only takes place during absorption.
LiFePO4 Float Voltage: Do You Need Float At All?
Victron, Battle Born and RELiON each publish a float voltage. Discover calls its float optional, and Fortress and SimpliPhi list no float for inverter charging.
Battery University, an educational site sponsored by Cadex Electronics, goes further. It lists float for LFP as "No charge" and writes: "Prolonged float charge on LFP batteries will shorten battery life."
We can't settle that for you. Your own battery's manual decides.
Max Charging Voltage For LiFePO4: The Cell Limit And The BMS
Battery University lists a maximum charge of 3.65 V per cell for LFP, or 14.6 V for a 12 V pack of 4 cells. Our own sum for 16 cells: 16 x 3.65 V = 58.4 V. Rolls recommends those same two figures for absorption.
Then there is a guard: the battery management system or BMS. Battle Born's sheet lists high voltage protection at 14.7 VDC, and Fortress's datasheet has the BMS disconnect charging above 56 V.
So what happens on a charger still set for flooded lead-acid? RELiON's instructions say those voltages are often higher than LiFePO4 requirements. The BMS then disconnects the battery at the end of the charge cycle, and the charger may show an error.
RELiON adds that this will typically not damage the battery.
Temperature Compensation And Equalization: Flooded Lead-Acid Yes, Victron And Rolls No
A profile for flooded lead-acid batteries has two extras. Trojan's User's Guide, in a copy hosted by a reseller, gives figures for its flooded ones.
The first is equalization, a maintenance charge at a raised voltage. Trojan lists 2.70 V per cell for it, against 2.45 V per cell for absorption and 2.25 V per cell for float, all at 25 °C.
The second is temperature compensation: the charger shifts its voltage with battery temperature. Trojan's figure is 5 mV per cell for each °C away from 25 °C, up when colder and down when warmer.
Two lithium manuals say the opposite. Victron's reads: "Temperature-compensated charging is not required for lithium batteries". Rolls tells owners to turn the setting off and disconnect the sensor.
On equalization, Rolls is just as firm: "Equalization should never be used; elevated charge voltages are unacceptable for LFP batteries."
LiFePO4 Charging Temperature Range: The Cold Limit Differs Too
The low end of the charging temperature range differs per maker. Victron's manual gives 5 to 50 °C for its Lithium Battery Smart and warns: "A lithium battery cell will sustain permanent damage when charged at temperatures below 5°C".
Discharge, taking power out, gets a wider range in the same manual: -20 to 50 °C.
Discover gives 0 °C to 45 °C for charging, and Rolls says never to charge a battery below 0 °C. RELiON differs: it lists -20 °C to 55 °C, with a reduced current below 0 °C.
- Charging allowed
- Charging at a reduced current
- Discharge only, hollow and dashed
- Grey: never charge
- Blue dashes: 0 °C
So Which Charging Voltage Do You Set?
The one in your own battery's manual. Victron's SmartSolar MPPT manual lists default settings for LiFePO4 batteries, and says they "can be adjusted if the battery manufacturer specifications advise otherwise".
Our charge controller guide covers the setup, and the controller size calculator sizes one for your panels. Have an experienced person check the settings and the wiring before the charger is switched on.
Sources
- Victron Energy, Lithium Battery Smart manual, rev 21
- Victron Energy, SmartSolar MPPT 100/30 and 100/50 manual
- Battle Born Batteries, BB10012 data sheet
- RELiON, Charging Instructions 08.28.18, copy at coastalclimatecontrol.com
- Rolls Battery, 12V and 24V LFP operating manual, copy at cdn.shopify.com
- Discover Battery, AES manual 805-0015 REV C
- Fortress Power, eVault Max technical datasheet, copy at cdn.shopify.com
- Morningstar, Fortress compatibility technote
- SimpliPhi Power, PHI 3.8 kWh 60 Amp specification sheet, copy at mrsolar.com
- Pylontech, US5000 operation manual, copy at cuencasolar.es
- Trojan Battery, User's Guide, copy at solacity.com
- Battery University, BU-409b: Charging Lithium Iron Phosphate
Hard Words
| Term | What it means |
|---|---|
| Bulk | The first charge stage. On Discover's charge curve it is a constant current up to the set voltage. |
| Absorption | The stage where the charger holds the set voltage, as on Discover's charge curve. |
| Float | The stage after absorption. Victron's manual says its battery is full when the charger reaches float and its app shows the cells as balanced. |
| BMS | Battery management system. Battle Born's sheet lists its high voltage protection at 14.7 VDC. |
| Equalization | A maintenance charge at a raised voltage. Trojan lists 2.70 V per cell for its flooded lead-acid batteries. |
Common Questions
What voltage should a 12V LiFePO4 battery be charged at?
The makers print different figures. Victron's manual gives 14.20 V absorption and 13.50 V float for its Lithium Battery Smart 12.8 V. Battle Born lists 14.2 V to 14.6 V absorption for its BB10012, and Rolls recommends 14.6 V for its 12 V LFP battery. Your own battery's manual decides.
What is the float voltage for a LiFePO4 battery?
It depends on the maker, and one source says to skip float. Victron's manual gives 13.50 V for its Lithium Battery Smart 12.8 V, Battle Born lists 13.4 V to 13.8 V for its BB10012 and RELiON 13.3 V to 13.8 V for a 12 V system. Battery University lists float for LFP as "No charge".
Can you use a lead-acid charger on a LiFePO4 battery?
It depends on the charger's voltages. RELiON's instructions say AGM and gel profiles typically fall within LiFePO4 voltage requirements, while flooded ones are often higher, so the BMS disconnects the battery. Rolls adds two checks for a lead-acid charger: no equalization, and temperature compensation off.
Is it bad to charge a LiFePO4 battery to 100%?
The makers we read do not agree, and we found no lab or university source on it. RELiON's instructions say LiFePO4 batteries "do not need to be fully charged" and advise storing them at 50% state of charge "to minimize irreversible capacity loss". Battle Born recommends bringing its batteries to a 100% charge before storage, and Discover's manual says 80%.