WHEN THE POWER GOES QUIET

Off-Grid Solar Troubleshooting: Why It Stopped Working

Energy Storage
Updated

Off-Grid Solar Troubleshooting Starts With The Symptom

Your system worked yesterday. This morning the lights stay dark, the fridge is warm and the inverter is beeping at you.

Off-grid solar troubleshooting sounds like a job for an expert, but most common problems follow a short route. A loose wire, a wrong setting or a battery that switched itself off to stay safe causes a lot of them. Victron's solar charger manual names loose connections again and again.

So start from what you see, not from what you fear.

What you noticeWhere to look first
No lights on the charge controllerBattery and panel voltage, fuses, breakers, cables
Controller on, but no chargingPanel voltage, settings, battery temperature
Charging, but the battery never fillsCable voltage drop, loads, settings, array size
Inverter beeps or shuts offLow battery, overload, loose DC cables
Everything goes dead at onceThe BMS on a lithium battery
A fuse or breaker keeps trippingA short, swapped wires, or a fault to stop for

Codes and limits differ per brand. Most numbers here come from Victron's manuals as an example, so keep your own manual open next to you.

Off-grid solar troubleshooting flow chartStart from what you see, with your own manual open. Over 50 V DC, a burned plug, or a hot or swollen battery? If yes: Stop, unless you're trained for it. Switch off what you safely can and call a qualified electrician. If no, go on. No lights on the charge controller? If yes: Check battery and panel voltage, fuses, breakers and cables, and that every connection is tight. If no, go on. Zero charge current, panel voltage near zero and a hot controller? If yes: Stop. The panel wires may be swapped: switch off and get help. If no, go on. Controller on, but no charging? If yes: Check panel voltage, settings and battery temperature. Victron's SmartSolar 150/60 to 250/70 start charging at 5 V above the battery; bigger units need more. Victron systems usually pause lithium charging below about 5 °C. If no, go on. Charging, but the battery never fills? If yes: Measure at the controller's battery terminals and at the battery: a difference over 2.5% is too much. Then check loads, settings and array size. If no, go on. Inverter beeps or shuts off? If yes: Low battery: charge it. Overload: switch off some loads. Then check for loose DC cables. If no, go on. Everything goes dead at once? If yes: Look at the BMS on a lithium battery: it may have cut the power to protect the cells. Have a charger ready. If no, go on. A fuse or breaker keeps tripping? If yes: Stop. Look for a short or swapped wires; a bigger fuse only takes the protection away. If a new fuse blows again right away, call an electrician. If none of these: Most of the time the fix is small: a tight terminal, a changed setting, or a battery that needed a charge.Start from what you see. Keep yourown manual open: codes and limitsdiffer per brand.Over 50 V DC, a burned plug,or a hot or swollen battery?YesStop, unless you'retrained for it. Switchoff what you safely canand call a qualifiedelectrician.NoNo lights on the chargecontroller?YesCheck battery and panelvoltage, fuses, breakersand cables, and thatevery connection istight.NoZero charge current, panelvoltage near zero and a hotcontroller?YesStop. The panel wires maybe swapped: switch offand get help.NoController on, but nocharging?YesCheck panel voltage,settings and batterytemperature. Victron'sSmartSolar 150/60 to250/70 start charging at5 V above the battery;bigger units need more.Victron systems usuallypause lithium chargingbelow about 5 °C.NoCharging, but the batterynever fills?YesMeasure at thecontroller's batteryterminals and at thebattery: a differenceover 2.5% is too much.Then check loads,settings and array size.NoInverter beeps or shuts off?YesLow battery: charge it.Overload: switch off someloads. Then check forloose DC cables.NoEverything goes dead at once?YesLook at the BMS on alithium battery: it mayhave cut the power toprotect the cells. Have acharger ready.NoA fuse or breaker keepstripping?YesStop. Look for a short orswapped wires; a biggerfuse only takes theprotection away. If a newfuse blows again rightaway, call anelectrician.NoMost of the time the fix is small: atight terminal, a changed setting,or a battery that needed a charge.
The checks on this page, in order. A yes leads to where to look first; a no takes you on to the next question. The boxes with a heavy border are stop points: switch off and get a pro. The numbers are Victron's, as an example, so check your own manual.

Measure Safely Before You Touch Anything

Electricians use a multimeter. That's a handheld box with two probes that tells you how much electrical push, called volts, sits in a wire.

Low voltage doesn't mean safe. Victron warns that anything over 50 volts DC is dangerous, and some of its solar chargers take up to 250 volts from the panels. Only qualified technicians should work on those.

Meter makers like Fluke give each meter a CAT rating, which says how well it survives a sudden voltage spike. Pick one rated above your panels' highest voltage, with room to spare.

Before each use, check the leads for cracked insulation and test the meter on something you know works. Then check plus and minus with it, because Victron warns a red cable isn't always plus.

Measuring volts with probes and amps with a clamp meterTwo sketches. Left: a multimeter's two probes touch the plus and the minus of a battery to read the volts. Right: a clamp meter hugs one wire, like a hair clip, to read the amps flowing in it, without touching bare metal. Never put the probes across a battery or panel while they are in the amps socket.Volts: probes acrossBatteryMeterTwo probesThe two probes touch plus and minus.Check plus and minus with the meter: ared cable isn't always plus.Amps: clamp around one wireBatteryClampSafer for amps: a clamp meter thathugs the wire, or a battery monitor.Never the probes across a battery orpanel in the amps socket.
Volts with the two probes across plus and minus; amps with a clamp around one wire. Pick a meter with a CAT rating above your panels' highest voltage, and remember that anything over 50 volts DC is dangerous. The rest of the circuit is not shown.

For amps, a clamp meter that hugs the wire like a hair clip, or a battery monitor, is safer. Never put the probes across a battery or panel while they're in the amps socket.

Solar Panel Not Charging Battery? Check The Controller

The charge controller is the traffic cop between panels and battery. It decides how much power goes in, and when to stop.

No lights and no app usually means it isn't getting enough voltage from the battery or the panels. Check cables, fuses, breakers and that every connection is tight. If it stays dark with good voltage on both sides, the unit may be faulty.

Lights on, but no charging

Victron's solar chargers are MPPT controllers. MPPT means maximum power point tracking: the controller keeps hunting for the sweet spot where your panels give the most power.

They also wait until the panels push harder than the battery. Victron's SmartSolar 150/60 to 250/70 manual says charging starts at 5 volts above battery voltage. It keeps going while the panels stay 1 volt above.

What pulls panel voltage down? Victron lists night, clouds, shade, dirt and a damaged panel. It adds a blown fuse, an open breaker, too few panels in series, swapped wires, or a loose or wrong MC4 connector, the click-together plug on panel cables.

Bigger units need more: Victron's Multi RS Solar needs 120 volts to start and 65 to keep running.

Sometimes it's off on purpose. A setting, a missing wire loop on the remote on/off connector or a lithium battery's BMS can stop it, and Victron systems usually pause lithium charging below about 5 °C to protect the cells.

And sometimes nothing is wrong. A full battery takes almost no current, and "externally controlled" just means another device is in charge.

Two readings that mean stop

Zero charge current, panel voltage near zero and a hot controller can mean the panel wires are swapped. Victron's charger shows no error for this, so switch off and get help.

Too much panel voltage is the other one. Panels push harder when they're cold, so Victron advises staying 10% below the controller's maximum. Go over and it shows error 33 and stops charging, and too much voltage can damage it for good.

Charging, But The Battery Never Fills Up

First, check that it really is low. Victron describes three stages: bulk fills the battery to about 80%, absorption tops it up to 100% and float holds it there. A battery monitor shows how full it really is.

Next, hunt for voltage drop. Electricity loses push in thin or loose cables, the way water loses pressure in a long, kinked garden hose. Measure the voltage at the controller's battery terminals, then at the battery itself.

Victron says a difference over 2.5% is too much. The fix is thicker cable, better crimps and tight terminals.

Measuring voltage drop between the charge controller and the batteryA charge controller is joined to a battery by a plus and a minus cable. One meter measures the voltage at the controller's battery terminals, a second one at the battery itself. Electricity loses push in thin or loose cables, so the battery reading is lower. Victron says a difference over 2.5% is too much; the fix is thicker cable, better crimps and tight terminals.ChargecontrollerbatteryterminalsBatteryV1V2At thecontrollerAt thebatteryCable runMore than 2.5% apart?Victron says a difference over 2.5% istoo much. Electricity loses push inthin or loose cables, the way waterloses pressure in a long, kinkedgarden hose.The fix is thicker cable, bettercrimps and tight terminals.
Measure the voltage at the controller's battery terminals (V1), then at the battery itself (V2). The cable in between loses some push, so V2 is lower; more than 2.5% apart is too much in Victron's manual. Check plus and minus with the meter, because a red cable isn't always plus.

Your appliances may be eating the sun. The battery only charges when the panels make more power than your loads use at that moment.

Then check the settings. Charge voltages or current set too low leave the battery short, and a lithium battery on a lead-acid setting is a classic mistake. For lithium, Victron says equalisation and temperature compensation must be off.

A wrong percentage on the monitor often means a wiring slip. Every load and charger must connect to the system side of the shunt, the little bar that counts amps, not straight to battery minus.

Maybe the array is simply too small. Victron says the battery should reach float every day, and its app keeps 30 days of history.

When the panels make less than they should

Compare the controller's best power of the day with your panels' rating. Big gaps usually mean shade, dirt or panels facing the wrong way.

Victron also lists mixed panel types, power optimisers that confuse the MPPT, and the wrong series or parallel layout. Heat counts too: that controller gives full output up to 40 °C and less above it.

Battery voltage sets a ceiling too: Victron's small 75/15 controller gives 180 watts on 12 volts, but 360 watts on 24.

Burned or melted panel plugs are a warning. Victron blames loose screws, thin or soldered cable, bad crimps, cheap MC4 plugs and over 30 amps through one plug pair. Stop and get help.

Why Your Off-Grid Inverter Keeps Shutting Off

An inverter is a translator box. It changes the battery's DC power into the AC power your sockets use.

On Victron's MultiPlus-II, a steady light means an alarm tripped and a flashing one means it was about to. Low battery means it switched off to protect the battery, while overload means too much power or a short. Charge, switch off some loads and try again.

When both lights flash together, Victron points at DC ripple. That's a wobble in battery voltage, like water sloshing in a bucket, and over 1.5 volts RMS (an AC reading of the DC wobble) is too much. Tighter connections, thicker cables or a bigger battery bank fix it.

A starting pump pulls a big burst of current, which shows as error 50 or 52 on Victron's Multi RS. Error 51 means it's too hot and needs better airflow.

Resetting is not a repair. For overload errors 50 and 52, the Multi RS gives up after three failed restarts, because the cause is still there.

Some codes are stop points. Error 57 means AC power was already on the output before switch-on, from the grid or another inverter.

Errors 41 and 42 mean electricity is leaking from the panel wiring, like a hole in a hose, and 43 points at an earth or wiring fault on the AC side. Don't keep resetting those.

When The BMS Cuts The Power

A lithium battery has a BMS, a battery management system. It works like a lifeguard for the cells and cuts the power to save them. Here's how to choose the right BMS.

Victron's Lynx Smart BMS switches the loads off when any cell drops below 2.8 volts, its default. They only come back when every cell reaches 3.2 volts.

If no charging power arrives within 5 minutes, that BMS switches itself off. Have a charger ready, then flip the remote switch off for 5 seconds and back on.

Charging that keeps stopping and starting is often cell imbalance. One cell fills faster than the others, like one kid in a relay team running way ahead.

When a cell hits 3.75 volts, the BMS switches the charger off, and back on below 3.6 volts. Victron says this can last up to 12 hours while the cells even out.

The cell voltages where a BMS switches loads and the charger off and onA scale of one lithium cell's voltage. On Victron's Lynx Smart BMS defaults, the loads switch off when any cell drops below 2.8 volts and only come back when every cell reaches 3.2 volts. The charger switches off when a cell hits 3.75 volts and back on below 3.6 volts. A cell below 2.5 volts is permanently damaged.Cell voltage3.75 V: charger off3.6 V: charger back on3.2 V: loads back on (every cell)2.8 V: loads off (any cell)below 2.5 V: damaged for goodVictron's Lynx Smart BMS, its defaultsThe loads only come back when everycell reaches 3.2 V. The charger comesback below 3.6 V, which can take up to12 hours while the cells even out.If no charging power arrives within 5minutes of a low-battery cut-off, thatBMS switches itself off. Have acharger ready.
Cell voltages from Victron's manuals: the Lynx Smart BMS defaults, and the 2.5 V damage limit for its lithium battery. Other brands use other numbers, so check your own manual. The spacing follows the voltages. Orange band: the gap where the charger stays off; grey band: the gap where the loads stay off.

An alarm while the cells look fine can be a loose or damaged BMS cable.

Two signs need the maker. A cell that ends up 0.1 to 0.2 volts below the others after a day of rest is probably defective. A 12 volt Victron lithium battery below 10 volts, or any cell below 2.5 volts, is permanently damaged.

Blown Fuses And Tripped Breakers

A fuse is the weakest link on purpose. It melts before your cables can overheat.

So a blown fuse or tripped breaker is a symptom. A bigger one doesn't fix the cause, it only takes the protection away. To get the size right, see what fuse you need.

Battery wires connected the wrong way round can blow the internal fuse in a Victron solar charger, and you can't replace that one yourself. A short on the load side is the other usual suspect.

On the Lynx Smart BMS, 6 red flashes every 4 seconds means pre-charge failed. Pre-charge is a gentle first trickle that fills an inverter's capacitors, tiny storage tanks, and a short or hungry load usually breaks it.

If a new fuse blows again right away, stop and call an electrician.

First Start-Up Checks For A New System

Plenty of faults are born on day one. Before switching on a new system, run these checks from Victron's manuals, in the order of our off-grid wiring guide.

  • Check battery polarity with a meter before you connect anything.
  • Set the right system voltage: 12, 24 or 48 volts. Victron warns that a setting higher than your battery, like 24 volts on a 12 volt battery, overcharges it.
  • Fit the wire loop on the remote on/off connector, or the unit stays off.
  • Set battery type and charge voltages from the battery maker's datasheet.
  • Keep the panels' open-circuit voltage 10% below the controller's maximum.
  • Victron advises connecting the DC system to earth at one point only, ideally at the battery. Earthing the panel frames and the AC side follows your installer's plan, not this rule.
  • Don't mix panel types, and leave optimisers out of an MPPT array.
  • Tighten every terminal properly, to the torque value in its manual.
  • For lithium, make sure the battery is warm enough to charge: about 5 °C on Victron's defaults.
  • Never connect the inverter's AC output to the grid or another inverter.

Open-circuit voltage, or Voc, is the push a panel makes with nothing connected. If your panel string stays under 50 volts DC, measure it on the panel cables before you connect them to the controller.

Installers test earthing, polarity, voltage and current per string of panels, and insulation, following IEC 62446-1, a test standard written for grid-connected systems that many installers also use as a checklist. If your panel string stays under 50 volts DC, you can check polarity and Voc yourself. Victron recommends fully insulated MC4 test leads, not bare probes. Above 50 volts, leave these tests to a pro too.

When To Stop And Call An Electrician

Some findings end the DIY part straight away. Switch off what you safely can and call a qualified electrician if you see:

  • Panel or battery voltage over 50 volts DC (that includes most 48 volt systems while charging), unless you're trained for it.
  • Burned, melted or discoloured plugs or terminals, or a smell of burning.
  • A swollen or hot battery, or a smell of acid or gas. Victron warns overcharging can cause explosion, fire or acid leaks.
  • An earth or insulation fault code.
  • A fuse that blows again right after you replace it.
  • A code that says the unit is faulty, to contact your dealer, or that a safety relay can't be reset.
  • A lithium battery below its maker's damage limits.
  • Anything on the mains side, or inside a closed enclosure.

Most of the time, though, the fix is smaller than the fear: a tight terminal, a changed setting, or a battery that needed a charge.

Sources

Hard Words

TermWhat it means
Charge controllerThe box between panels and battery that decides how much power goes in and when to stop.
MPPTMaximum power point tracking. A controller that keeps finding the setting where the panels give the most power.
MultimeterA handheld meter with two probes that measures volts, and with care amps.
PolarityWhich wire is plus and which is minus. Swapping them can blow fuses or damage equipment.
Voltage dropPush lost in thin or loose cables, like pressure lost in a long garden hose.
VocOpen-circuit voltage: what a panel pushes with nothing connected. It goes up when the panel is cold.
BMSBattery management system. It watches every cell in a lithium battery and cuts the power to protect them.
Cell imbalanceWhen one cell in a battery fills or empties faster than the others.
DC rippleA wobble in the battery voltage, often from loose connections or cables that are too thin.
Pre-chargeA gentle first trickle of power that fills an inverter's capacitors before full power flows.

Common Questions

Why is my solar panel not charging my battery?

Usually the panel voltage is too low, a connection is loose or a setting is wrong. Victron's SmartSolar controllers, for example, only start when the panels are at least 5 volts above the battery. Shade, dirt, a blown fuse, a loose MC4 plug or a full battery can all look like "not charging".

Why would my power go out if I have solar panels?

Usually the battery ran low and something switched off to protect it. The inverter shuts down on low battery voltage, and a lithium battery's BMS cuts the loads when a cell gets too low. Overloads, loose DC cables and a tripped fuse or breaker can also cut the power. Your inverter's lights or error code show which one.

How can I test if my solar panels are working?

Measure the open-circuit voltage (Voc) on the panel cables with a multimeter rated above your array's voltage, and compare it with the panel's label. Only do this yourself if the string is under 50 volts DC, and use insulated MC4 test leads. Then compare your controller's best power of the day with what the panels are rated for. Big gaps usually mean shade, dirt, a loose plug or a damaged panel.

How do I reset a solar charge controller?

Fix the cause first, because a reset alone doesn't repair anything. Many units restart on their own once the fault is gone. Victron's MPPT solar chargers, for example, clear most errors on their own once the cause is gone. If one stays, the manual says to disconnect the panels first, then the battery, wait 3 minutes, and reconnect the battery before the panels. Every brand differs, so follow the steps in your own manual.

Why does my inverter shut down when an appliance starts?

Motors like pumps pull a big burst of current when they start, and the inverter shuts down to protect itself. A weak or low battery and thin or loose DC cables make it worse. Charge the battery, run fewer loads at once and check the cables. Your manual's error code tells you which cause it is.

Why does charging stop and start when my lithium battery is nearly full?

Often it's cell imbalance. On Victron's lithium batteries, the BMS switches the charger off when one cell reaches 3.75 volts and back on below 3.6 volts. That cycle can last up to 12 hours while the cells even out. It's normal balancing, not a fault, unless one cell keeps dropping after rest.

When should I call an electrician for a solar fault?

Call one for voltages over 50 volts DC, burned or melted plugs, a hot or swollen battery, a smell of acid or burning, earth fault codes, or a fuse that blows again straight away. Also call for codes that say the unit is faulty, and for any work on the mains side.

On this page

Work it out